4.2.3.4 Evaluation des taux de charges des Postes et
Sous-stations pour
l'exercice 2005
|
TAUX DE CHARGES DES SOUS-STATIONS ET POSTES
|
Booster NR 15 I
|
Booster NR 15 II
|
ZIL 15 kV
|
UNILU 15 kV
|
AR 6.6 kV
|
Lubumbashi
|
Industrielle
|
Munama
|
Lukafu
|
|
Puissance installée
|
25
|
25
|
24
|
12
|
22
|
10
|
5
|
0.5
|
0.63
|
Puissance dispo
|
25
|
-
|
24
|
12
|
22
|
10
|
5
|
0.5
|
0.63
|
Janvier
|
PP
|
16.19
|
-
|
18.16
|
9.86
|
20.53
|
9.08
|
4.79
|
0.39
|
-
|
|
Tx
|
64.7
|
-
|
75.6
|
82.1
|
93.2
|
90.8
|
95.8
|
78
|
-
|
Février
|
PP
|
17.8
|
-
|
18.16
|
10.12
|
19.84
|
8.3
|
4.79
|
0.39
|
-
|
|
Tx
|
74.1
|
-
|
75.6
|
84.3
|
90.2
|
83
|
95.8
|
78
|
-
|
Mars
|
PP
|
17.8
|
-
|
18.16
|
10.12
|
19.84
|
8.3
|
4.79
|
-
|
-
|
|
Tx
|
74.1
|
-
|
75.6
|
84.3
|
90.2
|
83
|
95.8
|
-
|
-
|
Avril
|
PP
|
21.04
|
-
|
18.6
|
10.38
|
21.64
|
9.6
|
4.79
|
-
|
-
|
|
Tx
|
84.16
|
-
|
77.5
|
86.5
|
98.3
|
96
|
95.8
|
-
|
-
|
Mai
|
PP
|
21.04
|
-
|
19.46
|
10.38
|
21.54
|
9.39
|
4.79
|
-
|
-
|
|
Tx
|
80.2
|
-
|
81.1
|
86.5
|
97.9
|
93.9
|
95.8
|
-
|
-
|
Juin
|
PP
|
19.95
|
-
|
17.12
|
10.38
|
21.97
|
10.04
|
4.56
|
-
|
-
|
|
Tx
|
79.8
|
-
|
71.3
|
86.5
|
99.8
|
100.4
|
91.2
|
-
|
-
|
Tableau 4.7. Taux de
charges des Postes et Sous-stations
|
TAUX DE CHARGES DES SOUS-STATIONS ET POSTES
|
Booster NR 15 I
|
Booster NR 15 II
|
ZIL 15 kV
|
UNILU 15 kV
|
AR 6.6 kV
|
Lubumbashi
|
Industrielle
|
Munama
|
Lukafu
|
|
Puissance installée
|
25
|
25
|
24
|
12
|
22
|
10
|
5
|
0.5
|
0.63
|
Puissance dispo
|
25
|
-
|
24
|
12
|
22
|
10
|
5
|
0.5
|
0.63
|
Juillet
|
PP
|
19.85
|
-
|
19.46
|
9.86
|
23.12
|
10.27
|
4.56
|
-
|
-
|
|
Tx
|
79.4
|
-
|
84
|
82.1
|
105
|
102.7
|
91.2
|
-
|
-
|
Août
|
PP
|
21.04
|
-
|
24.9
|
9.86
|
22.02
|
10.04
|
4.22
|
0.45
|
8.85
|
|
Tx
|
84.1
|
-
|
103.7
|
82.1
|
100.9
|
100.4
|
84.4
|
90
|
134.9
|
Septembre
|
PP
|
22.68
|
-
|
23.74
|
9.99
|
22.6
|
10.73
|
4.22
|
0.45
|
0.85
|
|
Tx
|
90.7
|
-
|
98.9
|
83.2
|
102.7
|
107.3
|
84.4
|
90
|
134.9
|
Octobre
|
PP
|
22.13
|
-
|
22.49
|
9.73
|
23
|
10.96
|
4.22
|
0.45
|
0.85
|
|
Tx
|
88.5
|
-
|
93.7
|
81
|
104.5
|
109.6
|
84.4
|
90
|
134.9
|
Novembre
|
PP
|
21.04
|
-
|
24.98
|
9.86
|
21.75
|
10.12
|
4.22
|
0.45
|
0.85
|
|
Tx
|
84.1
|
-
|
104
|
82.1
|
98.8
|
101.2
|
84.4
|
90
|
134.9
|
Décembre
|
PP
|
19.43
|
-
|
23.74
|
9.73
|
21.1
|
9.6
|
4.22
|
0.45
|
0.79
|
|
Tx
|
77.7
|
-
|
98.9
|
81
|
95.9
|
96
|
94.4
|
90
|
125.3
|
Nombre de Feeders
|
15 kV
|
ES
|
5
|
-
|
6
|
5
|
|
3
|
|
|
|
HS
|
|
|
|
|
|
1
|
|
|
|
6.6 kV
|
ES
|
|
|
|
|
5
|
|
4
|
1
|
1
|
HS
|
|
|
|
|
|
|
2
|
|
|
Tableau 4.7. Taux de charges des Postes et
Sous-stations suite et fin
Tx = (en %)
(4.2)
Avec Tx : Taux de charges
PP : Puissance de Pointe
P dispo : Puissance disponible
Observation :
- Booster NR 15 II est mis hors service suite à
son mauvais fonctionnement.
- Le câble industriel se trouvant dans la
sous-station Lubumbashi est en défaut.
- Les câbles SGA et Kiwele se trouvant dans la sous-station
Industrielle sont en défaut.
- Nous n'avons pas prélevé certaines valeurs des
courants dans les sous-stations Munama et Lukafu par manque d'appareil